The international code council icc is a non profit organization dedicated to developing model codes and standards used in the design build and compliance process.
Ibc sliding door force.
The door shall be set in motion when subjected to a 30 pound 133 n force.
Both standards note that the 5 pound force limitation does not apply to the force required to retract latch bolts or disengage other devices that hold the door in a closed position refer to this decoded article for more information on the forces for operable hardware.
The maximum opening force for sliding and folding doors is also 5 pounds.
Sliding or folding doors 5 pounds of force.
So for an icu door its breakaway panels only open 90 degrees.
This means the width of the panel can only encroach 7 into the standard 8 foot wide corridor.
The ibc and nfpa 101 says a door at its fully open position cannot encroach more than 7 into the minimum requiredcorridor width.
Be 1010 1 3 1 location of applied forces.
Many of the requirements for manually operated sliding doors are the same as those for swinging doors but it s important to know where they differ.
For other swinging doors as well as sliding and folding doors the door latch shall release when subjected to a 15 pound 67 n force.
Opening force opening force for manually operated sliding and folding doors is limited to 5 pounds of opening force maximum.
This limitation does not include the force required to release the lock or latch.